-Schneider Electric Domae Surge Arrester PF 40 kA 1P+N - 16375
-
-[Deskrispsi]
- Surge Arrester tipe 2 yang direkomendasikan untuk melindungi peralatan elektronik residential (rumah tinggal) terhadap bahaya petir tidak langsung.
- Harus dikombinasikan dengan MCB 20A.
- Maximum Discharge Current (i max) 40kA pada 8/20s.
-
-[Spesifikasi]
-1. surge arrester class type - Type 2
-2. surge arrester technology - MOV + GDT
-3. [Ue] rated operational voltage - 230 V (+/- 10 %) AC 50/60 Hz
-4. [In] nominal discharge current-
- Common mode - 15 kA L/PE
- Common mode - 15 kA N/PE
-Differential mode - 15 kA L/N
-5. [Imax] maximum discharge current -
-Common mode - 40 kA L/PE
-Common mode - 40 kA N/PE
-Differential mode - 40 kA L/N
-6. [Uc] maximum continuous operating voltage -
- Common mode - 260 V N/PE
- Common mode - 340 V L/PE
-Differential mode - 340 V L/N
-7. [Up] voltage protection level -
- <= 1.5 kV type 2 common mode N/PE
- <= 1.5 kV type 2 differential mode L/N
-8. [Ut] temporary overvoltage-
-Withstand - 337 V L/N for 5 s
-Withstand - 442 V L/PE for 5 s
-Withstand - 1200 V N/PE for 200 ms
-Withstand - 1453 V L/PE for 200 ms
-9. disconnector device type - Associated circuit breaker Domae MCB 20 A Icu 6 kA curve C
-10. [Isccr] short-circuit current rating - 6 kA
-11. local signalling - LED color- green/red
-12. mounting mode - Clip-on
-13. mounting support - DIN rail
-14. 9 mm pitches - 2
-15. height - 81 mm
-16. width - 18 mm
-17. depth - 69 mm
-18. product weight - 125 g
-19. colour - Grey ( RAL 7035 )
-20. response time - <= 25 ns
-21. [Ipe] Ground residual current - <= 0.003 mA
-22. relative humidity - 5...95 %
-23. operating altitude - 2000 m
-24. connections - terminals -
- Tunnel type terminal, phase and neutral 1 cable(s) 25 mm
- Tunnel type terminal, ground 1 cable(s) 50 mm
-25. wire stripping length - 11 mm
-26. tightening torque - 3.5 N.m-